Event power demand calculator

Pick everything on your site that needs power – from the stage to the cold room. The calculator estimates the load with simultaneity, the current per phase, a suitable generator and the diesel consumption per day.

  • Free
  • No sign-up
  • Your input stays in your browser

Pick your consumers

Tap to add one, use − and + to change the count.

Stage & tech

Food

Drinks & cooling

Sanitary

Operations

Lighting

Camping

Rides

Recommended generator

?

Pick the consumers of your event on the left.

A planning aid using typical values of common rental equipment. A qualified electrician plans, installs and inspects the installation.

How the calculator estimates your power demand

Every consumer has a typical rated power in kilowatts. Because devices never all run at full load at the same time, the calculator multiplies each value by a simultaneity factor – different for a stage than for a cold room. Real power becomes apparent power with a power factor (cos φ) of 0.9.

Cooling units, pumps and rides draw a multiple of their rated current when starting. The calculator therefore keeps an extra reserve for the largest motor start.

  • Demand (kVA) = Σ kW × count × simultaneity ÷ 0.9
  • Current per phase = kVA × 1000 ÷ (√3 × 400 V), evenly distributed
  • Generator = smallest common size loaded to at most 80 % that also handles the largest start

Why 80 % and not 100 %?

A generator running at its limit all the time is risky: peaks, unbalanced phases and starting currents quickly cause an outage – in the middle of the headliner's set. A reserve of around 20 % is therefore common.

Too big is not good either: if a diesel generator runs below about 30 % load for long, the engine burns incompletely and soots up. A smaller generator, several sources or a grid connection is then the better choice.

Diesel consumption and CO₂

Consumption is made up of a base consumption that depends on the generator size and a load-dependent part. For CO₂ we use 2.65 kg per litre of diesel. Use the slider to set how many hours a day the power runs.

From the calculator to a power plan

The total tells you which size range to rent. A real plan needs more: where do the distribution boxes go, which cables cover which distance, how does the load split across the phases? A power plan on your site map answers these questions.

  • Place consumers on the map instead of counting them in a list.
  • Check cable lengths, voltage drop and phase load per run.
  • Derive the material list for the rental company.

The matching tools in Alpha Events

In the Alpha Events site map you place consumers on the real map, connect them to distribution boxes and generators and see load, cables and warnings live.

FAQ

Frequently asked questions

Questions about power planning for concerts, open airs and festivals.

Start for free
How big does the generator for my festival need to be?

That depends on all consumers. As a rule of thumb the generator should run at no more than about 80 % in operation and also handle the largest motor start – exactly how this tool calculates.

Where do the kW values come from?

They are typical planning values of common rental equipment. Data sheets or figures from your vendors are always more accurate.

What does current per phase mean?

A three-phase connection has three phases. The value shows how many amps each phase carries when the load is evenly distributed. In practice you have to split the loads across the phases.

Does the calculator replace electrical planning?

No. It helps with the size range and with comparing quotes. Planning, installing and inspecting the system belong in the hands of a qualified electrician.